Evap. condenser sizing output for Coil:Cooling:DX:SingleSpeed and TwoSpeed wrong labels #6353

Closed
3 tasks
asparke2 opened this issue Oct 5, 2017 · 0 comments · Fixed by #7427
Closed
3 tasks
Assignees
Labels
Defect Includes code to repair a defect in EnergyPlus

Comments

@asparke2
Copy link
Member

asparke2 commented Oct 5, 2017

Issue overview

The evaporative condenser outputs for Coil:Cooling:DX:SingleSpeed and Coil:Cooling:DX:TwoSpeed in the Initialization Summary -> Component Sizing Information have the wrong labels.

For the single speed coil below, per the I/O ref:

Cap = 127,473 W
Air Flow = 127,473 W * 0.000144 m3/s/W (autosized) = 18 m3/s
Pump Pwr = 127,473W * 0.004266 W/W (autosized) = 543 W

However, in the report:

543 is found labeled "Design Size Evaporative Condenser Air Flow Rate [W]"
14.5 is found labeled "Design Size Evaporative Condenser Effectiveness [m3/s]"
(not sure why the value is different than the autosized value, but probably a separate issue)

coilcoolingdxsinglespeedoutputerror

A similar pattern exists in the two speed coil:
coilcoolingdxtwospeedoutputerror

Details

  • Platform (Windows 7)
  • Version of EnergyPlus (8.8)

Checklist

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Defect file added (list location of defect file here)
  • Ticket added to Pivotal for defect (development team task)
  • Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)
@jmarrec jmarrec added the Defect Includes code to repair a defect in EnergyPlus label Jul 29, 2019
@jmarrec jmarrec self-assigned this Jul 29, 2019
jmarrec added a commit to jmarrec/EnergyPlus that referenced this issue Jul 30, 2019
jmarrec added a commit to jmarrec/EnergyPlus that referenced this issue Jul 30, 2019
rraustad added a commit that referenced this issue Aug 28, 2019
…XCoil

Fix #6353 - Evap. condenser sizing output for Coil:Cooling:DX:SingleSpeed and TwoSpeed wrong labels