Update 2ZoneDataCenterHVAC_wEconomizer.idf with ITE equipment and fix…
Browse files Browse the repository at this point in the history
… plant autosizing
  • Loading branch information
mjwitte committed Mar 20, 2015
1 parent ebb048b commit 5fa82e3
Showing 1 changed file with 190 additions and 75 deletions.
265 changes: 190 additions & 75 deletions testfiles/2ZoneDataCenterHVAC_wEconomizer.idf
Original file line number Diff line number Diff line change
Expand Up @@ -5,7 +5,7 @@
! Chilled Water Coil and VAV with No Reheat Air Terminal Unit.
!
! Mass walls. Regular slab floor. 2 Thermal Zones, and 2 supply plenum
! Regular roof. No Windows.
! Regular roof. No Windows. Air cooled IT equipment (ITE).
!
! Highlights: Example of single zone Airloop HVAC system for Data Center Application
!
Expand Down Expand Up @@ -59,7 +59,7 @@
! |__________________________________|
! (32.24,0,0) (32.24,15.24,0)
!
! Internal gains description: NA
! Internal gains description: Air cooled ITE and lights.
!
! Interzone Surfaces: None
! Internal Mass: None
Expand Down Expand Up @@ -1801,7 +1801,7 @@
CW Supply Outlet Node, !- Loop Temperature Setpoint Node Name
100, !- Maximum Loop Temperature {C}
3, !- Minimum Loop Temperature {C}
0.001, !- Maximum Loop Flow Rate {m3/s}
autosize, !- Maximum Loop Flow Rate {m3/s}
0, !- Minimum Loop Flow Rate {m3/s}
autocalculate, !- Plant Loop Volume {m3}
CW Supply Inlet Node, !- Plant Side Inlet Node Name
Expand Down Expand Up @@ -1983,8 +1983,8 @@
29.44, !- Design Condenser Inlet Temperature {C}
2.682759, !- Temperature Rise Coefficient
6.667, !- Design Chilled Water Outlet Temperature {C}
0.01, !- Design Chilled Water Flow Rate {m3/s}
0.01, !- Design Condenser Fluid Flow Rate {m3/s}
autosize, !- Design Chilled Water Flow Rate {m3/s}
autosize, !- Design Condenser Fluid Flow Rate {m3/s}
0.94483600, !- Coefficient 1 of Capacity Ratio Curve
-.05700880, !- Coefficient 2 of Capacity Ratio Curve
-.00185486, !- Coefficient 3 of Capacity Ratio Curve
Expand All @@ -2009,9 +2009,9 @@
CW Circ Pump, !- Name
CW Supply Inlet Node, !- Inlet Node Name
CW Pump Outlet Node, !- Outlet Node Name
0.005, !- Rated Flow Rate {m3/s}
autosize, !- Rated Flow Rate {m3/s}
160000, !- Rated Pump Head {Pa}
1000, !- Rated Power Consumption {W}
autosize, !- Rated Power Consumption {W}
0.87, !- Motor Efficiency
0.0, !- Fraction of Motor Inefficiencies to Fluid Stream
0, !- Coefficient 1 of the Part Load Performance Curve
Expand Down Expand Up @@ -2190,7 +2190,7 @@
Condenser Supply Outlet Node, !- Loop Temperature Setpoint Node Name
100, !- Maximum Loop Temperature {C}
3, !- Minimum Loop Temperature {C}
1.0, !- Maximum Loop Flow Rate {m3/s}
autosize, !- Maximum Loop Flow Rate {m3/s}
0, !- Minimum Loop Flow Rate {m3/s}
autocalculate, !- Plant Loop Volume {m3}
Condenser Supply Inlet Node, !- Plant Side Inlet Node Name
Expand Down Expand Up @@ -2696,46 +2696,6 @@
For: Sunday Holidays AllOtherDays, !- Field 32
Until: 24:00,0.30; !- Field 33

Schedule:Compact,
DataCenter_Equip_Sch,
Any Number,
Through: 1/31,
For: AllDays,
Until: 24:00, 0.25,
Through: 2/29,
For: AllDays,
Until: 24:00, 0.50,
Through: 3/31,
For: AllDays,
Until: 24:00, 0.75,
Through: 4/30,
For: AllDays,
Until: 24:00, 1.0,
Through: 5/31,
For: AllDays,
Until: 24:00, 0.25,
Through: 6/30,
For: AllDays,
Until: 24:00, 0.50,
Through: 7/31,
For: AllDays,
Until: 24:00, 0.75,
Through: 8/31,
For: AllDays,
Until: 24:00, 1.0,
Through: 9/30,
For: AllDays,
Until: 24:00, 0.25,
Through: 10/31,
For: AllDays,
Until: 24:00, 0.50,
Through: 11/30,
For: AllDays,
Until: 24:00, 0.75,
Through: 12/31,
For: AllDays,
Until: 24:00, 1.00;

ScheduleTypeLimits,
Any Number; !- Name

Expand Down Expand Up @@ -2766,20 +2726,120 @@
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory

ElectricEquipment,
WestDataCenter_Equip, !- Name
West Zone, !- Zone or ZoneList Name
DataCenter_Equip_Sch, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
200.0, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.2500, !- Fraction Radiant
0.0000, !- Fraction Lost
ITEquipMent; !- End-Use Subcategory
ElectricEquipment:ITE:AirCooled,
WestDataCenter_Equip, !- Name
West Zone, !- Zone Name
Watts/Area, !- Design Power Input Calculation Method
, !- Watts per Unit {W}
, !- Number of Units
200, !- Watts per Zone Floor Area {W/m2}
Data Center Operation Schedule, !- Design Power Input Schedule Name
Data Center CPU Loading Schedule, !- CPU Loading Schedule Name
Data Center Servers Power fLoadTemp, !- CPU Power Input Function of Loading and Air Temperature Curve Name
0.4, !- Design Fan Power Input Fraction
0.0001, !- Design Fan Air Flow Rate per Power Input {m3/s-W}
Data Center Servers Airflow fLoadTemp, !- Air Flow Function of Loading and Air Temperature Curve Name
ECM FanPower fFlow, !- Fan Power Input Function of Flow Curve Name
15, !- Design Entering Air Temperature {C}
A3, !- Environmental Class
AdjustedSupply, !- Air Inlet Connection Type
, !- Air Inlet Room Air Model Node Name
, !- Air Outlet Room Air Model Node Name
West Zone Inlet Node, !- Supply Air Node Name
0.1, !- Design Recirculation Fraction
Data Center Recirculation fLoadTemp, !- Recirculation Function of Loading and Supply Temperature Curve Name
0.9, !- Design Electric Power Supply Efficiency
UPS Efficiency fPLR, !- Electric Power Supply Efficiency Function of Part Load Ratio Curve Name
1, !- Fraction of Electric Power Supply Losses to Zone
ITE-CPU, !- CPU End-Use Subcategory
ITE-Fans, !- Fan End-Use Subcategory
ITE-UPS; !- Electric Power Supply End-Use Subcategory

Lights,
Curve:Quadratic,
ECM FanPower fFlow, !- Name
0.0, !- Coefficient1 Constant
1.0, !- Coefficient2 x
0.0, !- Coefficient3 x**2
0.0, !- Minimum Value of x
99.0; !- Maximum Value of x

Curve:Quadratic,
UPS Efficiency fPLR, !- Name
1.0, !- Coefficient1 Constant
0.0, !- Coefficient2 x
0.0, !- Coefficient3 x**2
0.0, !- Minimum Value of x
99.0; !- Maximum Value of x

Curve:Biquadratic,
Data Center Servers Power fLoadTemp, !- Name
-1.0, !- Coefficient1 Constant
1.0, !- Coefficient2 x
0.0, !- Coefficient3 x**2
0.06667, !- Coefficient4 y
0.0, !- Coefficient5 y**2
0.0, !- Coefficient6 x*y
0.0, !- Minimum Value of x
1.5, !- Maximum Value of x
-10, !- Minimum Value of y
99.0, !- Maximum Value of y
0.0, !- Minimum Curve Output
99.0, !- Maximum Curve Output
Dimensionless, !- Input Unit Type for X
Temperature, !- Input Unit Type for Y
Dimensionless; !- Output Unit Type

Curve:Biquadratic,
Data Center Servers Airflow fLoadTemp, !- Name
-1.4, !- Coefficient1 Constant
0.9, !- Coefficient2 x
0.0, !- Coefficient3 x**2
0.1, !- Coefficient4 y
0.0, !- Coefficient5 y**2
0.0, !- Coefficient6 x*y
0.0, !- Minimum Value of x
1.5, !- Maximum Value of x
-10, !- Minimum Value of y
99.0, !- Maximum Value of y
0.0, !- Minimum Curve Output
99.0, !- Maximum Curve Output
Dimensionless, !- Input Unit Type for X
Temperature, !- Input Unit Type for Y
Dimensionless; !- Output Unit Type

Curve:Biquadratic,
Data Center Recirculation fLoadTemp, !- Name
1.0, !- Coefficient1 Constant
0.0, !- Coefficient2 x
0.0, !- Coefficient3 x**2
0.0, !- Coefficient4 y
0.0, !- Coefficient5 y**2
0.0, !- Coefficient6 x*y
0.0, !- Minimum Value of x
1.5, !- Maximum Value of x
-10, !- Minimum Value of y
99.0, !- Maximum Value of y
0.0, !- Minimum Curve Output
99.0, !- Maximum Curve Output
Dimensionless, !- Input Unit Type for X
Temperature, !- Input Unit Type for Y
Dimensionless; !- Output Unit Type

Schedule:Constant, Data Center Operation Schedule, Any Number, 1.0;

Schedule:Compact,
Data Center CPU Loading Schedule, !- Name
Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 24:00,1.00, !- Field 3
For: AllOtherDays, !- Field 4
Until: 6:00,0.50, !- Field 5
Until: 8:00,0.75, !- Field 6
Until: 18:00,1.00, !- Field 7
Until: 24:00,0.80; !- Field 8

Lights,
East Zone Lights, !- Name
East Zone, !- Zone or ZoneList Name
LIGHTS-1, !- Schedule Name
Expand All @@ -2806,18 +2866,34 @@
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory

ElectricEquipment,
ElectricEquipment:ITE:AirCooled,
EastDataCenter_Equip, !- Name
East Zone, !- Zone or ZoneList Name
DataCenter_Equip_Sch, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
200.0, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
ITEquipMent; !- End-Use Subcategory
East Zone, !- Zone Name
Watts/Area, !- Design Power Input Calculation Method
, !- Watts per Unit {W}
, !- Number of Units
200, !- Watts per Zone Floor Area {W/m2}
Data Center Operation Schedule, !- Design Power Input Schedule Name
Data Center CPU Loading Schedule, !- CPU Loading Schedule Name
Data Center Servers Power fLoadTemp, !- CPU Power Input Function of Loading and Air Temperature Curve Name
0.4, !- Design Fan Power Input Fraction
0.0001, !- Design Fan Air Flow Rate per Power Input {m3/s-W}
Data Center Servers Airflow fLoadTemp, !- Air Flow Function of Loading and Air Temperature Curve Name
ECM FanPower fFlow, !- Fan Power Input Function of Flow Curve Name
15, !- Design Entering Air Temperature {C}
A3, !- Environmental Class
AdjustedSupply, !- Air Inlet Connection Type
, !- Air Inlet Room Air Model Node Name
, !- Air Outlet Room Air Model Node Name
East Zone Inlet Node, !- Supply Air Node Name
0.1, !- Design Recirculation Fraction
Data Center Recirculation fLoadTemp, !- Recirculation Function of Loading and Supply Temperature Curve Name
0.9, !- Design Electric Power Supply Efficiency
UPS Efficiency fPLR, !- Electric Power Supply Efficiency Function of Part Load Ratio Curve Name
1, !- Fraction of Electric Power Supply Losses to Zone
ITE-CPU, !- CPU End-Use Subcategory
ITE-Fans, !- Fan End-Use Subcategory
ITE-UPS; !- Electric Power Supply End-Use Subcategory

Schedule:Compact,
LIGHTS-1, !- Name
Expand Down Expand Up @@ -3058,14 +3134,53 @@
Output:Variable,East Zone Inlet Node,System Node Mass Flow Rate,timestep;
Output:Variable,East Zone Inlet Node,System Node Temperature,timestep;


Output:Variable,*,Evaporative Cooler Stage Effectiveness,timestep;
Output:Variable,*,Evaporative Cooler Total Stage Effectiveness,timestep;
Output:Variable, *,Evaporative Cooler Operating Mode Status, timestep;
Output:Variable,*,Evaporative Cooler Electric Power,timestep;
Output:Variable,*,Evaporative Cooler Water Volume,timestep;

Output:VariableDictionary,Regular;

Output:Variable,*,ITE CPU Electric Power,hourly; !- Zone Average [W]
Output:Variable,*,ITE Fan Electric Power,hourly; !- Zone Average [W]
Output:Variable,*,ITE UPS Electric Power,hourly; !- Zone Average [W]
Output:Variable,*,ITE CPU Electric Power at Design Inlet Conditions,hourly; !- Zone Average [W]
Output:Variable,*,ITE Fan Electric Power at Design Inlet Conditions,hourly; !- Zone Average [W]
Output:Variable,*,ITE UPS Heat Gain to Zone Rate,hourly; !- Zone Average [W]
Output:Variable,*,ITE Total Heat Gain to Zone Rate,hourly; !- Zone Average [W]
Output:Variable,*,ITE Standard Density Air Volume Flow Rate,hourly; !- Zone Average [m3/s]
Output:Variable,*,ITE Air Inlet Dry-Bulb Temperature,hourly; !- Zone Average [C]
Output:Variable,*,ITE Air Inlet Dewpoint Temperature,hourly; !- Zone Average [C]
Output:Variable,*,ITE Air Inlet Relative Humidity,hourly; !- Zone Average [%]
Output:Variable,*,ITE Air Outlet Dry-Bulb Temperature,hourly; !- Zone Average [C]
Output:Variable,*,ITE Supply Heat Index,hourly; !- Zone Average []
Output:Variable,*,ITE Air Inlet Operating Range Exceeded Time,hourly; !- Zone Sum [hr]
Output:Variable,*,ITE Air Inlet Dry-Bulb Temperature Above Operating Range Time,hourly; !- Zone Sum [hr]
Output:Variable,*,ITE Air Inlet Dry-Bulb Temperature Below Operating Range Time,hourly; !- Zone Sum [hr]
Output:Variable,*,ITE Air Inlet Dewpoint Temperature Above Operating Range Time,hourly; !- Zone Sum [hr]
Output:Variable,*,ITE Air Inlet Dewpoint Temperature Below Operating Range Time,hourly; !- Zone Sum [hr]
Output:Variable,*,ITE Air Inlet Relative Humidity Above Operating Range Time,hourly; !- Zone Sum [hr]
Output:Variable,*,ITE Air Inlet Relative Humidity Below Operating Range Time,hourly; !- Zone Sum [hr]
Output:Variable,*,ITE Air Inlet Dry-Bulb Temperature Difference Above Operating Range,hourly; !- Zone Average [deltaC]
Output:Variable,*,ITE Air Inlet Dry-Bulb Temperature Difference Below Operating Range,hourly; !- Zone Average [deltaC]
Output:Variable,*,ITE Air Inlet Dewpoint Temperature Difference Above Operating Range,hourly; !- Zone Average [deltaC]
Output:Variable,*,ITE Air Inlet Dewpoint Temperature Difference Below Operating Range,hourly; !- Zone Average [deltaC]
Output:Variable,*,ITE Air Inlet Relative Humidity Difference Above Operating Range,hourly; !- Zone Average [%]
Output:Variable,*,ITE Air Inlet Relative Humidity Difference Below Operating Range,hourly; !- Zone Average [%]
Output:Variable,*,Zone ITE CPU Electric Power,hourly; !- Zone Average [W]
Output:Variable,*,Zone ITE Fan Electric Power,hourly; !- Zone Average [W]
Output:Variable,*,Zone ITE UPS Electric Power,hourly; !- Zone Average [W]
Output:Variable,*,Zone ITE CPU Electric Power at Design Inlet Conditions,hourly; !- Zone Average [W]
Output:Variable,*,Zone ITE Fan Electric Power at Design Inlet Conditions,hourly; !- Zone Average [W]
Output:Variable,*,Zone ITE UPS Heat Gain to Zone Rate,hourly; !- Zone Average [W]
Output:Variable,*,Zone ITE Total Heat Gain to Zone Rate,hourly; !- Zone Average [W]
Output:Variable,*,Chiller Evaporator Cooling Rate,hourly; !- HVAC Average [W]
Output:Variable,*,Chiller Evaporator Inlet Temperature,hourly; !- HVAC Average [C]
Output:Variable,*,Chiller Evaporator Outlet Temperature,hourly; !- HVAC Average [C]
Output:Variable,*,Chiller Condenser Heat Transfer Rate,hourly; !- HVAC Average [W]
Output:Variable,*,Chiller Condenser Inlet Temperature,hourly; !- HVAC Average [C]
Output:Variable,*,Chiller Condenser Outlet Temperature,hourly; !- HVAC Average [C]

Output:VariableDictionary,IDF;

Output:Surfaces:Drawing,dxf;

Expand Down

7 comments on commit 5fa82e3

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

88939110-AddITEto2ZoneDataCenterExample-Issue4773 (mjwitte) - x86_64-MacOS-10.9-clang: OK (1663 of 1667 tests passed)

Build Badge Test Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

88939110-AddITEto2ZoneDataCenterExample-Issue4773 (mjwitte) - x86_64-Linux-Ubuntu-14.04-gcc-4.8: OK (1669 of 1673 tests passed)

Build Badge Test Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

88939110-AddITEto2ZoneDataCenterExample-Issue4773 (mjwitte) - x86_64-Linux-Ubuntu-14.04-cppcheck-1.61: OK (0 of 0 tests passed)

Build Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

88939110-AddITEto2ZoneDataCenterExample-Issue4773 (mjwitte) - x86_64-Linux-Ubuntu-14.04-gcc-4.8-UnitTestsCoverage-Debug: OK (653 of 655 tests passed)

Build Badge Test Badge Coverage Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

88939110-AddITEto2ZoneDataCenterExample-Issue4773 (mjwitte) - i386-Windows-7-VisualStudio-12: OK (1670 of 1673 tests passed)

Build Badge Test Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

88939110-AddITEto2ZoneDataCenterExample-Issue4773 (mjwitte) - x86_64-Linux-Ubuntu-14.04-gcc-4.8-IntegrationCoverage-Debug: OK (1163 of 1165 tests passed)

Build Badge Test Badge Coverage Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

88939110-AddITEto2ZoneDataCenterExample-Issue4773 (mjwitte) - Win64-Windows-7-VisualStudio-12: OK (1670 of 1673 tests passed)

Build Badge Test Badge

Please sign in to comment.