Modbus Tcp Binding

Kai edited this page Oct 20, 2013 · 20 revisions

Documentation of the Modbus TCP binding Bundle

Introduction

The modbus TCP binding polls the bus in an configurable interval for a configurable length.

For installation of the binding, please see Wiki page Bindings.

Details

Binding Configuration

add to ${openhab_home}/configuration/

Modbus binding allows to connect to multiple Modbus slaves as TCP master. This implementation works with coils (boolean values) only. Entries in openhab config file should look like below. Most of config parameters are related to specific slaves, the only exception is

 modbus:poll=<value>

which sets refresh interval to Modbus polling service. Value is in milliseconds - optional, default is 200

 modbus:<slave-name>:<slave-parameter>

{{{ is unique name per slave you are connecting to. are pairs key=value }}}

Valid keys are host mandatory port TCP port, optional, default 502 id slave id, optional, default 1 start slave start address, optional, default 0 length number of data item to read, default 0 (but set it to something meaningful :) type data type, can be either "coil", "discrete", "holding", "input" or "register", now only "coil", "discrete", "holding" and "input" is supported

now the modbus read function in case of {{{type=coil}}} is function 1, in case of {{{type=discrete}}} the read function is 2, in case of {{{type=holding}}} the read function is 3, in case of {{{type=input}}} the read function ist 4

writing is possible with {{{type=coil}}} the write function in this case is 5 and with {{{type=holding}}} the write function is 6 see also http://www.simplymodbus.ca

with {{{type=holding}}} and {{{type=input}}} you can now only operate with datatype byte!!! see below point 4

Minimal construction in openhab.config will look like

{{{ modbus:slave1.host=192.168.1.50 modbus:slave1.length=10 modbus:slave1.type=coil }}}

connects to slave on ip=192.168.1.51 and reads 10 coils starting from address 0 More complex setup could look like

modbus:slave1.host=192.168.1.50
modbus:slave1.port=502
modbus:slave1.id=41
modbus:poll=300
modbus:slave1.start=0
modbus:slave1.length=32
modbus:slave1.type=coil

example for an moxa e1214 module in simple io mode 6 output switches starting from modbus address 0 and 6 inputs from modbus address 10000 (the function 2 implizits the modbus 10000 address range) you only read 6 input bits and say start from 0 the moxa manual ist not right clear in this case

modbus:poll=300

modbus:slave1.host=192.168.6.180
modbus:slave1.port=502
modbus:slave1.id=1
modbus:slave1.start=0
modbus:slave1.length=6
modbus:slave1.type=coil

modbus:slave2.host=192.168.6.180
modbus:slave2.port=502
modbus:slave2.id=1
modbus:slave2.start=0
modbus:slave2.length=6
modbus:slave2.type=discrete

modbus:slave3.host=192.168.6.180
modbus:slave3.port=502
modbus:slave3.id=1
modbus:slave3.start=17
modbus:slave3.length=2
modbus:slave3.type=input

modbus:slave4.host=192.168.6.181
modbus:slave4.port=502
modbus:slave4.id=1
modbus:slave4.start=33
modbus:slave4.length=2
modbus:slave4.type=holding

here we use the same modbus gateway with ip 192.168.6.180 twice on different modbus address ranges and modbus functions

NOTE: the moxa e1200 modules give by reading with function 02 from start=0 the content of register 10000 aka DI-00, an reading with function code 1 gives the address 00000 this is a little bit scary, reading from other plc can be different!

Item Binding Configuration

ModbusBindingProvider provides binding for Openhab Items There are two ways to bind an item to modbus coils/registers

  1. single coil/register per item Switch MySwitch "My Modbus Switch" (ALL) {modbus="slave1:5"}

This binds MySwitch to modbus slave defined as "slave1" in openhab.config reading/writing to the coil 5

  1. separate coils for reading and writing Switch MySwitch "My Modbus Switch" (ALL) {modbus="slave1:<6:>7"} In this case coil 6 is used as status coil (readonly) and commands are put to coil 7 by setting coil 7 to true. You hardware should then set coil 7 back to false to allow further commands processing.

  2. input coil only for reading Contact Contact1 "Contact1 [MAP(en.map):%s]" (All) {modbus="slave2:0"} In this case regarding to moxa example coil 0 is used as discrete input (in Moxa naming DI-00)

following examples are relatively useless, if you know better one let us know! counter values in most cases 16bit values, now we must do math: in rules to deal with them ...

  1. read write byte register Number Dimmer1 "Dimmer1 [%d]" (ALL) {modbus="slave4:0"} and in sitemap Setpoint item=Dimmer1 minValue=0 maxValue=100 step=5 NOTE: if the value goes over a byte this case is fully untested!!! this example should write the value to all DO bits of an moxa e1212 as byte value

  2. read only byte register {{{type=input}}} Number MyCounterH "My Counter high [%d]" (All) {modbus="slave3:0"} this reads counter 1 high word Number MyCounterL "My Counter low [%d]" (All) {modbus="slave3:1"} this reads counter 1 low word

Installation


User Interfaces


Community

(link to openHAB forum)

Development



Misc


Samples

A good source of inspiration and tips from users gathered over the years. Be aware that things may have changed since they were written and some examples might not work correctly.

Please update the wiki if you do come across any out of date information.

Use case examples