Branch pumps show problems with autosizing. They do not track the flow rate size of a companion device on the branch. (CR #9215) #3986
Labels
Defect
Includes code to repair a defect in EnergyPlus
PriorityLow
This defect or feature has been declared low priority
SeverityMedium
This defect is medium severity, indicating moderate impact and generally no workaround available
Branch pump autosizing problem
Added on 2013-05-06 12:17 by @mjwitte
Description
From user ticket:
I have noticed a possible (I've been wrong before!) issue with the
autosizing of branch pumps:
When using the HVACTemplate for Chilled Water Loop,
If you use 'PumpPerChiller' or 'PumpPerTower' you get a pump that is
half the size it should be.
I have two chillers each with 0.5 sizing factor, and two Cooling
Towers with the same sizing factor.
In the attached file, when I use PumpPerChiller, I get two branch
pumps with a flow rate of 87.6 GPM each and one 350.5 GPM secondary pump
When I only change 'PumpPerChiller' to 'TwoHeaderedPumps' I get a
headered primary pump of 350.5 total GPM and single secondary pump of 350.5 gpm
In all of the above the reference evaporator flow rate for each
chiller was 175.3 gpm.
MJW 06 May 2013
Several test files based on the user file (all HVACTemplate), 1 chiller, 2 chillers 50-50, 2 chillers 25-75, 3 chillers 25-30-70. The branch pumps appear to be getting sized to the companion chiller flow divided by the number of parallel pumps (chillers). So, the 1 chiller with branch pump gets sized OK, but all of the others do not. Also, added one primary-only case to be sure that's not a factor (the others are all primary-secondary.)
Inputs: 9215-*
Weather: None - design days
Verification instructions: After fix, check the eio output. The autosized CHW BRANCH PUMP flow rates should match their respective chiller autosized Reference Chilled Water Flow Rate.
External Ref: Ticket 7343
Last build tested:
13.04.30 V8.0.0.008 - rerelease
The text was updated successfully, but these errors were encountered: